Don asked ... Find the charger or how to convert the battery?    |    Tanzania asked ... How can i mend my sanyo fwbp505f q?    |    Mark Goodwin asked ... Mount field 725m ride on mower?    |    Joan Sorrentino asked ... Barcalounger issue?    |    David asked ... Not starting until I bang door closed?    |    Click here to ask your question

boiler losing pressure?

a baxi genesis 80 losing pressure can anyone help.can open valve to get pressure but it drops below 1 bar
jacklab, October 2006
thanks, ran bioler flat out pressure dropped from 3 to 2half and also the overflow pipe was dripping outside, should this happen or does it give you a better idea of my problem....thanks

jacklab, November 2006
repressurise, run heating flat out and see if the pressure rises up to 3 then loses pressure, if so, the expansion vessel either needs repressurising or the diaphragm inside it has gone in which case it will need a new vessel

MIKE, October 2006
could be loosing it through the expansion vessel bladder split

hi-spec plumbing, October 2006
within 4 hours it looses pressure, no leaks found

jacklab, October 2006
how quick does it loose pressure ? must have a leak in system some where. need more info

hi-spec plumbing, October 2006