katlego asked ... Rev count on my 1982?    |    andrew asked ... "SECURE" on a yellow backround, and I cant ge?    |    Melodie asked ... How do I remove and change the basket? Duratech Identity Gu?    |    Kathy asked ... Samsung ER-4915?    |    Mark asked ... Oven door removal?    |    Click here to ask your question

Expansion tank hot?

Greenstar Ri boiler open vented system. When boiler switched on constant flow of hot water to expansion tank through vent pipe. Circulation through rads still OK but seems reduced. Cold water feed ok and rad circlation pipes clear. Could this be partial blockage in heat exchanger if so how do you clear it? Service manual shows how it remove but only to brush out flue ducts. Any other causes? Have tried pump on lower speeds.
kenav, November 2012
Blocked pipe need clean up,try restorer sentinel ,drain down system pour 2 Lt no need to drain out, also lift vent pipe 1meter

ltd, November 2012