HT asked ... Radio code Philips 22RC200/35?    |    Roberta asked ... DW5080?    |    Dave asked ... Toilet Push Button not flushing properly?    |    Dave asked ... Repair kettle lid?    |    Sandy asked ... Replace vertical gear on Singer Fashion Mate 252?    |    Click here to ask your question

Ideal combi boiler isar he24?

How do we reduce the pressure on the boiler it should read 1-1.5 but it reads 3 abit worried about it blowing up!!!
Donna, March 2013
Donna im a gas engineer,it won't blow up,it goes out side after 3.5-4 bar of pressure.uts either over pressurising or the vessel has gone or the filling loop is open,meaning someone has topped the system up with water and left the valve open,but with that boiler,you'll find its the vessal

Martin, March 2013