Dave asked ... Repair kettle lid?    |    Sandy asked ... Replace vertical gear on Singer Fashion Mate 252?    |    Blaablaa asked ... How can I fix?    |    pete asked ... Flymo 330 turboglide?    |    keith asked ... Fuseboard( s) location of renault trafic t1100 1993?    |    Click here to ask your question

Greenstar 12i?

Hi, I have a Greenstar12i system boiler - When the room stat is turned up the boiler starts up and the burner comes on. It heats up for 20 secs or so, then burner knocks off and pump still circulates, but will not fire back up. Replaced primary thermostat and top limit thermostat, but no different - any ideas!
Patrick, May 2013
found the cause to be the siphon bottle had blocked up with gunge.

Patrick, May 2013