Sandy asked ... Replace vertical gear on Singer Fashion Mate 252?    |    Blaablaa asked ... How can I fix?    |    pete asked ... Flymo 330 turboglide?    |    keith asked ... Fuseboard( s) location of renault trafic t1100 1993?    |    Janet asked ... Neff B1641 door not closing at top?    |    Click here to ask your question

how to tell if motorised valve needs replacing?

boiler fires and reaches temperature but does not cut out.room thermostat turns off at required temperature but radiators keep getting hotter . is there a fault on the motorised valvef
mark, December 2013
If you have 2 two port valves turn the stat to full, park yourself by the valve that is for the heating then get someone to turn on heating after a short while you might hear a click and the boiler should fire up.depending on type of valve you may be able to see it operating then get the other person to turn stat down to zero, valve should close immediately.If its a 3 port valve you would need to access the connection box and disconnect the orange wire

toptrish, December 2013