Sandy asked ... Replace vertical gear on Singer Fashion Mate 252?    |    Blaablaa asked ... How can I fix?    |    pete asked ... Flymo 330 turboglide?    |    keith asked ... Fuseboard( s) location of renault trafic t1100 1993?    |    Janet asked ... Neff B1641 door not closing at top?    |    Click here to ask your question

potterton promax?

I have to top my promax 24 he plus boiler up every day when the heating is on the pressure goes right up to 4 which means water is running out of the pressure relief and when it cools it is down to under 1 bar
Dave, December 2013
thanks toptrish

Dave, December 2013
There is no air in the expansion vessel which is either in the boiler or as a separate [red ] tank.To find out how check you tube [recharging an expansion vessel ]

toptrish, December 2013