David Dawes asked ... How to recoil the starter spring - Champion R484TR?    |    peter high asked ... How can I set time on my Neff oven?    |    Michael asked ... Mountfield empress drive belt?    |    John Barton asked ... How do i clear the TAM?    |    John asked ... How can I mend my binatone veva 1210 handset?    |    Click here to ask your question

Vaillant boiler won't stay 'on'?

My Vaillant CH boiler 242 EB Combi - LPG fuel from 2x87kg cylinders
Refuses to stay on; when the heating is on and I run the HW tap it clicks off immediately (red light next to ignition button comes on). It's driving me mad as the boiler is in the loft in our small cottage and I have to keep traipsing up there to switch it on again. The heat exchanger and gas outlets in the burners have been cleaned recently and all pressures are fine. Any suggestions, PLEASE!!!
Peter A Davis, February 2014
A possible solution, it's not the boiler but the supply. The boiler running ch generally runs a a lower rate of gas consumption, when the hw is called for that rate ramps up significantly due to the 'instant' requirement for hw.
I can only suggest you check the supply bottles, tubes, changeover valve and governors are correct before condemning the boiler.

Carefree, February 2014