Blaablaa asked ... How can I fix?    |    pete asked ... Flymo 330 turboglide?    |    keith asked ... Fuseboard( s) location of renault trafic t1100 1993?    |    Janet asked ... Neff B1641 door not closing at top?    |    Steve asked ... Gilera runner 180 vxr 2001 ignition replacement?    |    Click here to ask your question

My Vaillant VCW GB 280 H combi-boiler, pump keeps running ?

The pump on my Vaillant some times keeps running after the heating and hot water demand have switched off?
The hot water and heating is working OK except for this.
This seems to happen more so after the hot water has been running for a long time.
Phil, February 2014
The VCW pump timer is able to be set from 1-12 minutes, it comes factory set at 5 minutes, if the pump runs on (after any use), for approximately 5 minutes, it is working as designed and you may be looking for a fault that doesn't exist

Carefree, March 2014