Blaablaa asked ... How can I fix?    |    pete asked ... Flymo 330 turboglide?    |    keith asked ... Fuseboard( s) location of renault trafic t1100 1993?    |    Janet asked ... Neff B1641 door not closing at top?    |    Steve asked ... Gilera runner 180 vxr 2001 ignition replacement?    |    Click here to ask your question

glow work swiftflow 75/80/100?

I have no hot water or CH. Problem started after removing a radiator to decorate a spare room. Low pressure light is flashing although 1.5 bar ATM. Fan is running, I bypassed flow switch and that seems to work. Any ideas? I have tried bleeding the pipes for the removed rad and another rad in a different room. The boiler doesn't fire when the taps are turned on but sounds like it does when CH switched on. However, no heat in rads when left on for 30 mins.
Help?????!
pete, May 2014
Try bridging out switch on water pressure switch could be blocked internally with sediment

a, May 2014
Pump runs when taps switched on and when central heating is turned on but no heat.
Pressure switch?

pete, May 2014
Check is pump running
Check system pressure switch

a, May 2014
link Click here to see other fixes for 80/100.