Blaablaa asked ... How can I fix?    |    pete asked ... Flymo 330 turboglide?    |    keith asked ... Fuseboard( s) location of renault trafic t1100 1993?    |    Janet asked ... Neff B1641 door not closing at top?    |    Steve asked ... Gilera runner 180 vxr 2001 ignition replacement?    |    Click here to ask your question

Can you repressure the Expansion vessel on the Baxi 28 HE combi boiler?

How Can I recharge expansion vessel
Jim Wilson, January 2015
There is a valve on the top of the vessel ( the same as a car tyre ) just pump it up to 1 bar but you will have to open the expansion relief valve and keep it open to drop the water pressure in the central heating system before you attempt it so that you are not pumping against the system pressure, the expansion vessel may be full of water so that has to be forced out as you are pumping air in,I have got a portable power station with a built in pump when i do expansion vessels on unvented hot water tanks it makes the job easier

toptrish, January 2015