Don asked ... Find the charger or how to convert the battery?    |    Tanzania asked ... How can i mend my sanyo fwbp505f q?    |    Mark Goodwin asked ... Mount field 725m ride on mower?    |    Joan Sorrentino asked ... Barcalounger issue?    |    David asked ... Not starting until I bang door closed?    |    Click here to ask your question

105e over pressure?

my baxi 105e goes to about 3 bar when central heating is on this causes the pressure relief valve to operate and empty the water out of the closed loop. so have o keep filling the boiler every day . i have change the relief valve and it is still doing it. can someone help please. thanks dave.
david brown, December 2006
expansion vessel has discharged its air,you need to pump it back up

stu, December 2006