Carol asked ... How to remove roller from lawnmower?    |    Ariana Orellana asked ... Code?    |    Lynnie asked ... BT Studio 4500 cordless telephone?    |    David Dawes asked ... How to recoil the starter spring - Champion R484TR?    |    peter high asked ... How can I set time on my Neff oven?    |    Click here to ask your question

Sime super 120 de luxe - high pressure problem?

Hi, I have read a few similar questions on this site, so appologies if this is not new, but here we go..

The pressure on my Sime super 120 de luxe goes from 1 bar to 3 bar when the heating is switched on - and then water leaks from the safety valve. When the heating is switched off, the pressure returns to 1 bar (ok, a bit less than that due to the lost water). Replies to similar questions have suggested a leaky heat enchanger leaking mains water into the central heating system, but i'm not sure this makes sense in this case as the pressure drops after the heating is turned off...

Two other clues:
- The pressure problem has gradually been getting worse over a few weeks, but it has only just started to hit the 3 bar level and start leaking.
- I think the start of this problem coincides with the point at which the temperature gauge stopped working - or is that just coincidence?

Any advice on how to fix this please?
Thanks,
Mark.
(01/01/2007)
Mark Veryard, January 2007
Great - thanks for your help!

I'll take a look and see if that fixes it.

Mark.

Mark Veryard, January 2007
sounds like your expansion vessel needs recharging, on the vessel is a valve like a car tyre if you place a gauge on to it it should read approx 1bar. you can use a car foot pump to get pressure back up but system must be empty of water

hi-spec plumbing, January 2007