1 hour ago Don asked ... Find the charger or how to convert the battery?    |    Tanzania asked ... How can i mend my sanyo fwbp505f q?    |    Mark Goodwin asked ... Mount field 725m ride on mower?    |    Joan Sorrentino asked ... Barcalounger issue?    |    David asked ... Not starting until I bang door closed?    |    Click here to ask your question

how do I fix my riello 40 boiler after running out of oil?

I ran out of oil, i have oil now but the boiler fires up and then dies
Tracey Smyth, March 2007
you need to purge the oil throught to the oil pump as it sound like u have air in the line after running out u can do this by finding the screw on the oil pump marked v or p loosen the allen screw slightly and allow the air to be purged from the oil line do not remove screw as when oil comes out you might not be able to replace it hope this helps

steve, March 2007