Sandy asked ... Replace vertical gear on Singer Fashion Mate 252?    |    Blaablaa asked ... How can I fix?    |    pete asked ... Flymo 330 turboglide?    |    keith asked ... Fuseboard( s) location of renault trafic t1100 1993?    |    Janet asked ... Neff B1641 door not closing at top?    |    Click here to ask your question

i just took off a radiater to tile behind, now i need to bleed the air out?

i just took off a rad, and now need to bleed the air out the system, its a vaillant combi boiler model vcw t3w sein 18, how do i get the air out and water back in?
tony, April 2007
Re-connect rad, open rad valves, open the air vent on the rad, turn on the water at the filling loop.

Get the air out (water will show when the rad is full) turn off filling loop.

job done

George, April 2007
use bleed screw on all radiators in house over a few days. System will refill

sherb, April 2007
link Click here to see other fixes for Vaillant.