Sandy asked ... Replace vertical gear on Singer Fashion Mate 252?    |    Blaablaa asked ... How can I fix?    |    pete asked ... Flymo 330 turboglide?    |    keith asked ... Fuseboard( s) location of renault trafic t1100 1993?    |    Janet asked ... Neff B1641 door not closing at top?    |    Click here to ask your question

ravenheat CSI 85A combi boiler. flame blowing out soon after ignition?

boiler is 2 years old. it starts normaly (fan starts, ignition clicks, pilot comes on then main burner ignights) After 30 seconds the main burner stops and the boiler then goes through the start up cycle, however the main flame ignights for an instant then seems to "blow out" This is not wind related.
Could this be the thermocouple faulty and not allowing the main burner to stay on? Any suggestions would be appreciated
Ian, August 2007
Had similar problems on same model last year on 18 month old boiler. Problem found to be electronic board fault. New board fitted problem solved. If your unit only has a 12 month warrenty try to claim costs under the Sale of Goods Act ,this can be done on line(Money claim) and worked for me reclaiming £210 + cost of action £30.
Keep all receipts, ask repairer for brief written confirmation of defect, and keep defective part for examination if requested.
Good luck

Alan, August 2007
it is dhw and ch.

Ian, August 2007
is this on dhw

if so poss dhw sensor

sonray heating, August 2007
link Click here to see other fixes for Ravenheat.