Sandy asked ... Replace vertical gear on Singer Fashion Mate 252?    |    Blaablaa asked ... How can I fix?    |    pete asked ... Flymo 330 turboglide?    |    keith asked ... Fuseboard( s) location of renault trafic t1100 1993?    |    Janet asked ... Neff B1641 door not closing at top?    |    Click here to ask your question

has my pressure switch gone on my baxi solo wm 50/4 pf?

my pilot light is going and the fan kicks in ok but no main burners ignite. I have replaced the solenoid and gas valve as per the baxi fault finder but i'm thinking now its teh pressure switch. anyone any thoughts?
Simon, October 2007
Just had a flame failure problem on BAXI MAIN 24HE,changed electrodes no fix.
Engineer changed air pressure switch BAXI 5112999
Working ok.This boiler leaked through seals from flow and return pipes after 6 months .The heateam engineer explained that it was a common BAXI problem where the sealing washers go brittle !!!!!! Nice one BAXI

mrfixa, June 2009
also its not a dedicated pilot on these is it,its electronic ignition so no pilot should be there as such.possible electrode? if you can hear the boiler trying to ignite id change pilot assenbly including electrode.if not look at air pressure switch tubes,air pressure switches rarely fail

reuben, November 2007
check the hoses to the air pressure switch,they are renowned for going brittle and splitting.
happened twice in two years for me.causes air leak and air pressure switch not activating then no ignition.

reuben, November 2007