Tanzania asked ... How can i mend my sanyo fwbp505f q?    |    Mark Goodwin asked ... Mount field 725m ride on mower?    |    Joan Sorrentino asked ... Barcalounger issue?    |    David asked ... Not starting until I bang door closed?    |    Sharma asked ... Replacing pin for belt guard Ranch King Pro 14AT818H205?    |    Click here to ask your question

halstead ace tap water not getting hot?

central heating ok
when dhw selected water stays cold
no leds come on
model 47333-10 ace
dink, October 2007
dhw diaphragm in large brass unit r/h side of boiler. check if dhw m/switch is being shut (l/h side of diverter valve in clear case). if it isn`t being shut then diaphragm is torn or 2 chrome pipes r blocked causing false reading.