Tanzania asked ... How can i mend my sanyo fwbp505f q?    |    Mark Goodwin asked ... Mount field 725m ride on mower?    |    Joan Sorrentino asked ... Barcalounger issue?    |    David asked ... Not starting until I bang door closed?    |    Sharma asked ... Replacing pin for belt guard Ranch King Pro 14AT818H205?    |    Click here to ask your question

Myson Apolo 30s does this use 240v mains switching?

I have had to replace the main timer on my central heating system. I have gone for a siemens RWB7 electronic timer, the system will still not activate (boiler is fine). The only thing I can think that it would be is that I need to link the Live to one of the control circuit wires which is an option for 240v mains switching. When I moved into the house there was no boiler manual and cannot find one online.
Any ideas? Do not want to just link them and do something drastically wrong!
Marc A, October 2007
You need to link the timer feed (the brown wire)to the common terminal on the heating and hot water switch on the timer ie
heating n/o common n/c. hot water n/o common n/c.

allen, June 2008
link Click here to see other fixes for Myson Apolo 30s.