Blaablaa asked ... How can I fix?    |    pete asked ... Flymo 330 turboglide?    |    keith asked ... Fuseboard( s) location of renault trafic t1100 1993?    |    Janet asked ... Neff B1641 door not closing at top?    |    Steve asked ... Gilera runner 180 vxr 2001 ignition replacement?    |    Click here to ask your question

Solenoid vale not opening?

Trianco/Monoflame Minor/Danfoss pump(new)
Pump changed due to fault, now the solenoid valve remains closed not allowing fuel to flow ! Lock-out does not "lock-out" but ignitor and fan work OK. HELP !!!
Mark Golledge, December 2007
Hi Mark
Have the solenoid valve coil checked and prove there is a signal getting to it from the control box. Also check that the pump has been vented and fully primed. Has the operating oil pressure been set correctly on the new pump.

D.R., January 2008