4 hours ago Sandy asked ... Replace vertical gear on Singer Fashion Mate 252?    |    Blaablaa asked ... How can I fix?    |    pete asked ... Flymo 330 turboglide?    |    keith asked ... Fuseboard( s) location of renault trafic t1100 1993?    |    Janet asked ... Neff B1641 door not closing at top?    |    Click here to ask your question

Riello RDB Boiler - bleeding it after oil ran out?

Hi

I read some other posts and I think I get it but want to check one thing - the bleed valve is it approx 3 inches long, hexagonal in shape with a inset screw in the end which I suspect undoes with an allen key. Do I loosen that and hit the reset button until oil flows then tighten it and hopefully thats it?

Thanks

Andy
Andy, January 2008
Thanks for the help guys, boiler now bled

Andy the Brave, May 2012
William, thanks u so much. this just worked a treat, i was messing about with the filter trying to bleed it until i foundthis post.

happy days...heat and water!!!!! hallieula!

Sean, June 2011
Here is a photo of one. It may help you to describe.

[img]http://i3.photobucket.com/albums/y79/TaraChoules/Image034-1.jpg[/img]

TKC, March 2008
Hi Andy,

Yes, you've got it. Just one thing, keep the valve open until you hear the burner start to ignite, then tighten. This is because oil starts to leave the valve before the boiler ignites. This helps to ensure the air has been purged and the burner has enough oil to start up properly.

William, February 2008
link Click here to see other fixes for Riello.