20 mins ago Ariana Orellana asked ... Code?    |    Lynnie asked ... BT Studio 4500 cordless telephone?    |    David Dawes asked ... How to recoil the starter spring - Champion R484TR?    |    peter high asked ... How can I set time on my Neff oven?    |    Michael asked ... Mountfield empress drive belt?    |    Click here to ask your question

Riello RDB Boiler - bleeding it after oil ran out?

Hi

I read some other posts and I think I get it but want to check one thing - the bleed valve is it approx 3 inches long, hexagonal in shape with a inset screw in the end which I suspect undoes with an allen key. Do I loosen that and hit the reset button until oil flows then tighten it and hopefully thats it?

Thanks

Andy
Andy, January 2008
Thanks for the help guys, boiler now bled

Andy the Brave, May 2012
William, thanks u so much. this just worked a treat, i was messing about with the filter trying to bleed it until i foundthis post.

happy days...heat and water!!!!! hallieula!

Sean, June 2011
Here is a photo of one. It may help you to describe.

[img]http://i3.photobucket.com/albums/y79/TaraChoules/Image034-1.jpg[/img]

TKC, March 2008
Hi Andy,

Yes, you've got it. Just one thing, keep the valve open until you hear the burner start to ignite, then tighten. This is because oil starts to leave the valve before the boiler ignites. This helps to ensure the air has been purged and the burner has enough oil to start up properly.

William, February 2008