dave s asked ... Transmission not working?    |    Tom asked ... Replace rear right door upper right latch cable - high roof?    |    ian asked ... Vaillant timeswitch 150 analogue unit (clock stopped?    |    Art Cour asked ... How do I get engine cowling off to find gas leaking?    |    liz asked ... Changing a belt?    |    Click here to ask your question

pressure drop/increase baxi 105 e?

any help please. Always had a pressure drop on this boiler. keep topping up . thinking of using a sealer . Are they any good. added prob though. I noticed when checking pressure other day whilst Ch was on that the pressure went from 1.5 to over 2 and rising. Steadied when i turned heating off. Could the system be draining itself via pressure releif valve if pressure kept rising to ver 3 bar. And why would it rise
graham coulton, March 2008
yes it could, why not leave a bucket outside under the relief pipe to test if your loosing it there.

It would rise over 3bar from 1bar while heating if the expansion vessel was knackered.

T, March 2008