14 mins ago Tom asked ... Service manual for Lawnflite 908LA?    |    John asked ... Scantronics 9450 box stuck shut?    |    Pekaye asked ... Clutch Cable change?    |    Richard asked ... Mountfield SP414 mower, revs too high?    |    Don asked ... Find the charger or how to convert the battery?    |    Click here to ask your question

Valliant boiler making noises?

Our vallient boiler has, for a while, been cutting out with either error code f22 or f24 (don't know the model, can't find it anywhere on the boiler). The pressure guage reads normal. We have been making use of our emersion heater, but now that has stoped working and it sounds like its boiling dry. Now it is making noises like there is air in the system (similar to what a radiator makes when it needs bleeding, or a washing machine filling with water). The noises have got louder during the day, so I switched the boiler off at the mains. The noises stops, but I could here air escaping from somewhere for a brief while afterwards.

Can anyone help? THere is a cold snap supposedly coming this weekend and we have guests visiting and our plumber won't come till next week..
Ian Sudbery, April 2008
Sounds like you may need a circ pump head.....

Both F22 & F24 are low water alarms...

F22 - Low Water or No Water in the Appliance
F24 - Water Level Low - Temp Rises too fast

If you want a copy of the EcoMAx Manual just email me
tony@oilburnerservices.com

Do not run your boiler, as you could end up cooking your heat exchanger and blowing it's thermal trip...then ud need a new heat exchanger too....

T, April 2008