42 mins ago Don asked ... Find the charger or how to convert the battery?    |    Tanzania asked ... How can i mend my sanyo fwbp505f q?    |    Mark Goodwin asked ... Mount field 725m ride on mower?    |    Joan Sorrentino asked ... Barcalounger issue?    |    David asked ... Not starting until I bang door closed?    |    Click here to ask your question

no hot water or central heating?

I do not have any hot water or central heating, the boiler does not fire up at all yet the pilot light is lit, the programmer works, the water pump starts and the diverter valve moves position to put the central heating on. The room thermastat and the hot water thermastat both work? the boiler is a myson apollo.
any one have any ideas?
thanks
Steve, September 2008
you'd have to see if the boiler is getting its live supply from the motorised valve, is it getting power to high/low stat is it getting power to gas valve.

if its got power to pump then good chance power is down to boiler and therefore id be looking at high/low stat control and gas valve to determine fault

iain, September 2008