Blaablaa asked ... How can I fix?    |    pete asked ... Flymo 330 turboglide?    |    keith asked ... Fuseboard( s) location of renault trafic t1100 1993?    |    Janet asked ... Neff B1641 door not closing at top?    |    Steve asked ... Gilera runner 180 vxr 2001 ignition replacement?    |    Click here to ask your question

worcester 26cdi preasure gauge abvoe 3bar over flow dripping?

dropped presure via relife valve but it still gose back up
even if c/h is off,preasure gose up quicker if c/h is on.
help please.
shaun, October 2008
it sounds as though the plate heat exchanger is cross leaking and putting mains water pressure into the heating side.
If pressure is rising when boiler isn't running and filling loop key is removed then this is more than likely the problem, hope it helps.

joe, October 2008
thanks-filling loop valve(gery knob)offand key removed.
shall i try c/h on mains water off and see what happens to preasure then?

shaun, October 2008
Your filling loop must be still letting water through disconnect or you may have valve to turn off

stephen armstrong, October 2008