Dave asked ... Repair kettle lid?    |    Sandy asked ... Replace vertical gear on Singer Fashion Mate 252?    |    Blaablaa asked ... How can I fix?    |    pete asked ... Flymo 330 turboglide?    |    keith asked ... Fuseboard( s) location of renault trafic t1100 1993?    |    Click here to ask your question

How can i fix my sime friendly format 80E boiler?

When turning on the Central Heating and leaving it for approx. 30mins, the pressure keeps going over the blue zone onto 3 bars. I have bled all rads so no air in the system.

Can anyone please advise? Thanks.
Sohail, November 2008
sounds like the expansion vessel is broken , easy way to test it is to find valve on expansion vessel , its a small tyre valve on top of vessel . remove valve cap and depress pin in valve , if water comes out diaphragm in vessel has failed and vessel must be replaced . hope this helps

christian boiler man, November 2008
link Click here to see other fixes for Sime.