Don asked ... Find the charger or how to convert the battery?    |    Tanzania asked ... How can i mend my sanyo fwbp505f q?    |    Mark Goodwin asked ... Mount field 725m ride on mower?    |    Joan Sorrentino asked ... Barcalounger issue?    |    David asked ... Not starting until I bang door closed?    |    Click here to ask your question

pressure too high ?

my ariston boiler goes too 3 bar from 1 bar idle
rj, December 2008
either the filling loop is passing or the heat exchanger is split, also look at the expansion vessel check it is pressurised.

richofix, January 2009
expansion vessel is either depleted of air or its hole'd...drain boiler check air charge in vessel with foot pump (should be round 1 bar) if its empty then pump to 1 bar

mark the gay boiler man, December 2008
link Click here to see other fixes for Ariston Pro One.