Don asked ... Find the charger or how to convert the battery?    |    Tanzania asked ... How can i mend my sanyo fwbp505f q?    |    Mark Goodwin asked ... Mount field 725m ride on mower?    |    Joan Sorrentino asked ... Barcalounger issue?    |    David asked ... Not starting until I bang door closed?    |    Click here to ask your question

low pressure?

icos m3080 boiler. some of our radiators aren't getting hot while others seem fine, the pressure gauge seems to indicate low pressure but i'm not sure which of the 3 valves to use to increase it -i assume it's the one by the pressure gauge?
Mib Evans, December 2008
I'm not familiar with your particuler boiler but if you have three valves I would guess one is the flow pipe, one on the return pipe and the third will be to mains pressure cold water - probably by the gauge. If you have the boiler running then both flow and return pipes should be hot which will hopefully confirm the cold one as your water supply. Let the system cool down before you add pressure and then add it slowly probably to between 11/2 bar and 2 bar (see your instruction book if you have one). Good luck

Richard, December 2008