Sandy asked ... Replace vertical gear on Singer Fashion Mate 252?    |    Blaablaa asked ... How can I fix?    |    pete asked ... Flymo 330 turboglide?    |    keith asked ... Fuseboard( s) location of renault trafic t1100 1993?    |    Janet asked ... Neff B1641 door not closing at top?    |    Click here to ask your question

Combi boiler starts up when I run the cold tap?

I have a Worcester 24I combi boiler, I have noticed when I run the cold tap then turn it off the boiler starts running, it doesn't fire up, just the pump starts by the sound of it.

Does anyone have any idea's or a solution please.

Any help would be greatly appreciated.

Regards Garry
Garry Woodhouse, August 2009
The back pressure when you shut off the cold tap is triggering the dhw flow switch in the boiler. Have a plumber or gas engineer fit a mini expansion vessel onto the cold water supply pipe just below the boiler, this should be enough to cushion the back pressure and cure the fault.

Ian, August 2009
link Click here to see other fixes for Worcester 24i.