Don asked ... Find the charger or how to convert the battery?    |    Tanzania asked ... How can i mend my sanyo fwbp505f q?    |    Mark Goodwin asked ... Mount field 725m ride on mower?    |    Joan Sorrentino asked ... Barcalounger issue?    |    David asked ... Not starting until I bang door closed?    |    Click here to ask your question

POTTERTON LYNX 2 BOILER?

I have a problem with this rotten boiler, as many before have noted most of the boards has been replaced and now we only get hot water when we put the heating up to 20 or higher. Does any one have any ideas as to how to correct this without it costing an arm and a leg?
Will B, August 2009
From brief explained symptoms, I would say the hot water divertor is faulty. This is a component that reconizes you are running hot water. However, if diaphram split your boiler will not fire for hot water. This is a cheap part to buy approx £11.00.
An engineer should be able to complete this repair no more than two hours.

Rob, RJS Heating Ltd www.rjsheating.co.uk, August 2009
Craig
The Potterton Lynx 2 is a combi boiler!
Will b.
You want to look at the HW flow switch (Back right)

Mr Boiler, August 2009
IS IT A COMBI BOILER OR DO U HAVE A HOT WATER CYLINDER

CRAIG, August 2009