15 mins ago Pekaye asked ... Clutch Cable change?    |    1 hour ago Richard asked ... Mountfield SP414 mower, revs too high?    |    Don asked ... Find the charger or how to convert the battery?    |    Tanzania asked ... How can i mend my sanyo fwbp505f q?    |    Mark Goodwin asked ... Mount field 725m ride on mower?    |    Click here to ask your question

can you add another socket to a spur?

can you add another socket to a junction box spur which already has a socket
joe, October 2009
on a ring final circuit you can spur like for like,that is you can spur a new socket from the ring, this is as per the j box, if you want to take more than this then you have to fuse accordingly at the point of the spur. where the socket is taken from the j box, fit a fused connection at this point max fuse 13a bs1362 (plug fuse), then take the socket from this, as the new sockets are fused at 13amp the cable wont be overloaded, assuming that, the j box is 30amp rated, the circuit does not exceed the the max Zs ie 80% 0f 1.44ohms at the farest end of the circuit for a 32amp mcd type b rule of thumb, and that the circuit is protected by rcd either at the consumer unit or rcd fused connection unit, finally would always reccommend getting someone qualified in to do the work.

sparkiefc, October 2009
Yes, but only if it is appropriately fused.

Adam, October 2009
no

ali, October 2009