Tanzania asked ... How can i mend my sanyo fwbp505f q?    |    Mark Goodwin asked ... Mount field 725m ride on mower?    |    Joan Sorrentino asked ... Barcalounger issue?    |    David asked ... Not starting until I bang door closed?    |    Sharma asked ... Replacing pin for belt guard Ranch King Pro 14AT818H205?    |    Click here to ask your question

The pressure guage on the bolier has gone to maximum, how can I get it back?

I have just returned from a holiday to find my boiler making a weird sound and the pressure gauge is at 4 (which is the maximum).
It is a glow worm combi boiler.
Is there something I can do to reduce the pressure?
Sarah, October 2009
Get the expansion vessel . Will need to be pumped up

John

John, October 2009
Its curious that the pressure didn't release at 3 bar - this is the usual. Reduce pressure by bleeding water off at the radiators - it will take a while but its the most boiler friendly way. Make sure the filling loop isn't slightly open to prevent it pressurising again.

John, October 2009