Don asked ... Find the charger or how to convert the battery?    |    Tanzania asked ... How can i mend my sanyo fwbp505f q?    |    Mark Goodwin asked ... Mount field 725m ride on mower?    |    Joan Sorrentino asked ... Barcalounger issue?    |    David asked ... Not starting until I bang door closed?    |    Click here to ask your question

my Glow-worm combi boiler keeps over pressurizing when on?

when i start my my Glow-worm combi boiler the pressure rises from 1.8 bar to 3 bar setting the prv off then it dumps the water out the overflow
john m, November 2009
I suspect this is the pressure vessel needs recharging it has no air in it or it could need replacing.Another common fault on this particular boiler is the chrome braided hose connecting the pressure vessel to the primary circut is blocked this will need removing and cleaning out probably a good exercise to do both.This will solve the problem.

Mark Heatline, January 2010