Don asked ... Find the charger or how to convert the battery?    |    Tanzania asked ... How can i mend my sanyo fwbp505f q?    |    Mark Goodwin asked ... Mount field 725m ride on mower?    |    Joan Sorrentino asked ... Barcalounger issue?    |    David asked ... Not starting until I bang door closed?    |    Click here to ask your question

Hello all, boiler not working properly?

Hello all, i have a very old combi c.h boiler (solaire model ghb 21/f t.02) which no one has heard of, i would guess at least 15 if not 20 yrs old. two probs with it heating seems fine but losing pressure ( will run ok on with zero pressure, which i'm sure is not right) bleed rads and top up weekly, have located small leak to diverter valve (prob 2), hot water tempremantal often running lukewarm , can coax hot water by turning on and off a few times and running water slowly. I would like to change the diverter valve (diaphram switching ok) to get it running whilst saving for replacement. problem is i do not know which one to get, .have found one in b.e.s catalogue (page 118 in the pic it looks identical to dvo-d) but there are 4 diff dvo-d types . only markings on mine are H70787 any help appreciated.
tom scratching his head, February 2010
Ok , no replies so dived in,,took old diverter valve out and took to plumbing shop, chap at counter sold replacement (worcester 240 model) fitted it problem one solved.. unscrewed main feed to expansion vessel with basin spanner( very tricky) was able to extract vessel upwards and out, re-charged to 2 bar using footpump, replaced (even trickier) working fine, no pressure loss. job done..

tom not scratching anymore, March 2010