Freya asked ... Frister & Rossman Cub7 Sewing Machine?    |    katlego asked ... Rev count on my 1982?    |    andrew asked ... "SECURE" on a yellow backround, and I cant ge?    |    Melodie asked ... How do I remove and change the basket? Duratech Identity Gu?    |    Kathy asked ... Samsung ER-4915?    |    Click here to ask your question

problem with combi boiler due to low water pressure?

Hi our worcester bosch combination boiler has stopped working. we think due to low water pressure - the dial is at zero. Any ideas?
gareth price, February 2010
i have same problem, I can not find the switch to re-fill the water....PLEASE HELP!!!

LISA, March 2010
Hi, Check all rad valves for leaks, but it could also be a sympton of a leaking pressure relief valve. You will need to locate the PRV pipe (15mm copper, always outside, usually near the boiler) you can tape a freezer bag to it. This will show you if it is passing water. Top up pressure and check daily. If not either of these, probable expansion vessel loss of pressure. You will need to call someone, but at least you will have an idea of the problem..Good luck.

Mike, February 2010
I have had the same problem, cause was a leaking radiator valve, you may have a leak somewere causing pressure to drop.

Graham, February 2010
top up pressure.

x, February 2010