Carol asked ... How to remove roller from lawnmower?    |    Ariana Orellana asked ... Code?    |    Lynnie asked ... BT Studio 4500 cordless telephone?    |    David Dawes asked ... How to recoil the starter spring - Champion R484TR?    |    peter high asked ... How can I set time on my Neff oven?    |    Click here to ask your question

Cant re-pressurise my saunier duval isofast condens f35e?

The pressure in my system has dropped to 0.5 bar so I have an error message 21 and no hot water or heating.

The boiler manual says to gently open the blue filling tap to re-pressurise but when i do this i cant hear any water entering the boiler and water starts to drip out from the drain cock.

Help!!
Simon Gardner, February 2010
turn the blue filling cock open and switch the boiler off then on at the power socket, repeat switching on and off till pressure is back up to 1.5 bar........the water dripping will stop when cock is closed again

GMB, March 2010
you need a new filling cock, they are well known for being faulty. either that or have an external filling loop fitted.

Ian, February 2010
link Click here to see other fixes for Saunier Duval.