saunia duval combi f30e pressure build up?

pressure increasing when running central heating saftey valve opening looseing water until pressure drops then boiler cuts out
Richard, March 2010
Expansion vessel may need Re-charging or pipe to expansion vessel may be blocked.

To re-charge vessel:-
Open safety valve (keep open)
Put bike pump onto expansion vessel (if water comes out of connection vessel may be faulty). Pump up to 1 bar.
Close safety valve and re pressurise system.