Morne asked ... My defy dtl 125 toploader?    |    Ernie asked ... How to fix gearchange ldv maxus van 2006?    |    Cuckoo asked ... Changing batteries on a fixed bt corded phone?    |    Marc Nollid asked ... Nissan Micra mk 5 2018 rear seat mecanism?    |    Maggie asked ... New Home 535?    |    Click here to ask your question

Boiler pressure too low then too high!?

Hi. Recently the pressure in my boiler constantly drops to practically zero. To turn the heating on I release water into the boiler to bring the pressure back up to 1 bar. After the heating being on for about 15 minutes the pressure shoots up to over 3 bar at which stage I turn off the heating so it doesn't explode. The pressure quickly drops to below 1 bar again. Does anyone know what could be causing this?
Gerty, March 2010
the expansion vessel is kaput

ian, March 2010
your boiler expansion vessel is possibly EMPTY and needs a recharge of AIR via a car foot pump,find the valve on expansion vessel, remove the cap,test pressure then inflate via the car valve to about 1 bar, or approx 15 psi. then re pressurize the waterside backup to 1 to 1.5 bar