3 hours ago Sandy asked ... Replace vertical gear on Singer Fashion Mate 252?    |    Blaablaa asked ... How can I fix?    |    pete asked ... Flymo 330 turboglide?    |    keith asked ... Fuseboard( s) location of renault trafic t1100 1993?    |    Janet asked ... Neff B1641 door not closing at top?    |    Click here to ask your question

Sime Format Friendly 80 (2000 model)?

Hi,

I'm getting water ok with the above boiler, but no heating - electrics seem to be working fine. I think the pressure is a little low.
Anything a complete novice can do without a pro?

Cheers

Tim
Tim, May 2006
hi, the boiler pressure must be over 1bar ie 1.5 bar is good,the boiler has a low pressure cut off, top up the pressure carefully via the fill up loop pipe/valve.and all should be back to normal.
take care and do not play with the gas [bang]. ok bob rob.

bob rob, May 2006