katlego asked ... Rev count on my 1982?    |    andrew asked ... "SECURE" on a yellow backround, and I cant ge?    |    Melodie asked ... How do I remove and change the basket? Duratech Identity Gu?    |    Kathy asked ... Samsung ER-4915?    |    Mark asked ... Oven door removal?    |    Click here to ask your question

Valiant F22 low pressure problem?

Afer a day out, i came home to have a shower only to find cold water coming out. I checked the bolier and had F22 low pressure warning. I have reset the boiler however it only regains to 0.5 bar. Any idea how i can increase in the pressure in the system?

I have not changed anything in the house. The boilier is about 1.5 years old.
Rhys, June 2010
lok under the boiler there should be two small black levers attached to a small pipe(5mm), trun both on 1/4 trun you will hear water running in to the boiler when the gage reads 1.5 bar turn both off and boiler should run ok.

erj, June 2010