Sandy asked ... Replace vertical gear on Singer Fashion Mate 252?    |    Blaablaa asked ... How can I fix?    |    pete asked ... Flymo 330 turboglide?    |    keith asked ... Fuseboard( s) location of renault trafic t1100 1993?    |    Janet asked ... Neff B1641 door not closing at top?    |    Click here to ask your question

Worcester Bosch Thermotechnik 280 RSF - The heating system pressure gauge?

Lowering the pressure - heating system pressure gauge.?
I have this boiler and i cant seam to get the pressure to go down to the correct position. How can i do this? I have looked on the internet all evening for a fix and I cant seam to find the answer i want. Does anyone know how I can do this? (PS: it is getting very cold in the house :( and no hot water!)

It keeps raising to the max and cutting out,,,

Please help!!!! - Thanks everyone!!!!
A VERY cold Shad, November 2010
you need to have your expansion vessel repressurised, that is causing your water pressure problem. also if you have no hot water then you most likley need a new diaphragm in your diverter valve.

Ian, November 2010
I have the answer,,, lol.. bleed the radiators!!! Eurikaa!!!!

Research not wasted...

A Happy and Warm Shad, November 2010