Blaablaa asked ... How can I fix?    |    pete asked ... Flymo 330 turboglide?    |    keith asked ... Fuseboard( s) location of renault trafic t1100 1993?    |    Janet asked ... Neff B1641 door not closing at top?    |    Steve asked ... Gilera runner 180 vxr 2001 ignition replacement?    |    Click here to ask your question

how can i fix worcester-bosch greenstar 25si?

when the heating is on the boiler normally runs at 1 bar pressure but now for some reason when the heating is on it is running at 2.5 bar pressure is there a problem?
mike, November 2010
I have a worcester boiler 24 green star and the condensation pipe froze up and the boiler stopped working. I have defrosted the boiler dryed out the in side and the boiler will not fire up

Derek, December 2010
sounds like the expansion vessel has either lost its pre-charge pressure, or the bladder in it has split (if latter, you'll need a new vessel sorry).

Take the dust cap off the vessel's schreider valve (similar to a car tyre cap/valve) and press the pin in gently. If you get air, fine. If you get water, the bladder is split.

CMac, December 2010