Dave asked ... Toilet Push Button not flushing properly?    |    Dave asked ... Repair kettle lid?    |    Sandy asked ... Replace vertical gear on Singer Fashion Mate 252?    |    Blaablaa asked ... How can I fix?    |    pete asked ... Flymo 330 turboglide?    |    Click here to ask your question

what is the problem?

vaillant turbo plus 828E. There is no power to block4 and when I connect power to it the pump comes on and the boiler fires up but only remains on for a minute.
tom hughes, November 2010
First time mis-read No power to 4 = external fault
But:
sounds like you have two problems, if the boiler only fires for a minute with power to 4, watch for diverter valve movement when connecting power to 4 (through the hole on the side of the valve), sounds like the diverter is not opening to the CH side

Carefree, November 2010
No power to terminal block 4 means the fault is external to the boiler ie: Timer/room stat.

The power is fed from the boiler terminal 3, through the external controls and back to terminal 4

Carefree, November 2010
link Click here to see other fixes for Vaillant.