Don asked ... Find the charger or how to convert the battery?    |    Tanzania asked ... How can i mend my sanyo fwbp505f q?    |    Mark Goodwin asked ... Mount field 725m ride on mower?    |    Joan Sorrentino asked ... Barcalounger issue?    |    David asked ... Not starting until I bang door closed?    |    Click here to ask your question

boiler bangs when zones shut down?

i have a new gwa hot water boiler model 175ns with 4 honeywell zone valves v8043e1012 controled with a argo az4cp when any zone shuts off i get a bang in the area of the valves it happens even right after i bleed each zone
macko, February 2011
It sounds like the new pump is too powerful, forcing the valves shut/open.
Look to fit a small system by-pass on the primary flow/return pipework.

Carefree, February 2011