Tom asked ... Service manual for Lawnflite 908LA?    |    John asked ... Scantronics 9450 box stuck shut?    |    Pekaye asked ... Clutch Cable change?    |    Richard asked ... Mountfield SP414 mower, revs too high?    |    Don asked ... Find the charger or how to convert the battery?    |    Click here to ask your question

Lifestyle mid position valve?

Hot water and heating come on but after a while heating shuts off and if increase thermostat nothing happens to rads. manually pushing mid position valve then send heat to rads. Is this thermostat problem?
Jerry Cotton, April 2011
When the heating shuts off after the short period, test for 220-240v at the diverter valve white wire, if there is power there, the most likely outcome is the actuator motor is failing.
If there is no power on the white wire, it would indeed be the room thermostat.

Carefree, April 2011