1 hour ago Don asked ... Find the charger or how to convert the battery?    |    Tanzania asked ... How can i mend my sanyo fwbp505f q?    |    Mark Goodwin asked ... Mount field 725m ride on mower?    |    Joan Sorrentino asked ... Barcalounger issue?    |    David asked ... Not starting until I bang door closed?    |    Click here to ask your question

my britony combi boiler has blown the internal fuses?

The boiler has blown the 3rd internal fuse when replaced blown again. no heating or hot water can it be fixed
stu, August 2011
firstly the cause of the fault has to be found. what i would do in this case is disconnect all the connections from the pcb board. then replace the fuse. turn back on the power and see if the fuse blows. turn back off the power and plug in each componant individually until you determin which one is blowing the fuse. ie is it the pump, the fan, air pressure switch, then replace the faulty part. hope this helps.

plumb bob, August 2011