Carol asked ... How to remove roller from lawnmower?    |    Ariana Orellana asked ... Code?    |    Lynnie asked ... BT Studio 4500 cordless telephone?    |    David Dawes asked ... How to recoil the starter spring - Champion R484TR?    |    peter high asked ... How can I set time on my Neff oven?    |    Click here to ask your question

my britony combi boiler has blown the internal fuses?

The boiler has blown the 3rd internal fuse when replaced blown again. no heating or hot water can it be fixed
stu, August 2011
firstly the cause of the fault has to be found. what i would do in this case is disconnect all the connections from the pcb board. then replace the fuse. turn back on the power and see if the fuse blows. turn back off the power and plug in each componant individually until you determin which one is blowing the fuse. ie is it the pump, the fan, air pressure switch, then replace the faulty part. hope this helps.

plumb bob, August 2011