1 hour ago Sandy asked ... Replace vertical gear on Singer Fashion Mate 252?    |    Blaablaa asked ... How can I fix?    |    pete asked ... Flymo 330 turboglide?    |    keith asked ... Fuseboard( s) location of renault trafic t1100 1993?    |    Janet asked ... Neff B1641 door not closing at top?    |    Click here to ask your question

Security lighting?

i have just got a security light that is supposed to be connected using a switched fused spur, but the light i am replacing is fitted to the lighting circuit. will it make any difference if the new light is fitted to the lighting circuit
coops, October 2006
It shouldn't do. In the UK at least, all lighting circuits should ne fused to 5 or 6 amps which obviates the need for a fused spur. Some security lights, however, require a switched spur in order to set them to the required mode.
You can usually achieve this by using your MCB if your consuner unit features one.

Juan Skinner, October 2006
mine are.

kd, October 2006