Sandy asked ... Replace vertical gear on Singer Fashion Mate 252?    |    Blaablaa asked ... How can I fix?    |    pete asked ... Flymo 330 turboglide?    |    keith asked ... Fuseboard( s) location of renault trafic t1100 1993?    |    Janet asked ... Neff B1641 door not closing at top?    |    Click here to ask your question

problem on b9 burner unit?

i have a oil boiler b9 burner unit ,burner keeps locking out ,have not got any power to coil lead fitted new lead , new photo cell and lead, and c/box checked wires connections stuck what els to try ,any thoughts thanks.
kevin, January 2012
no power to the oil pump solenoid ?
has to be a faulty control box, if a new photocell fitted.
you should have in sequence
fan spinning, ignition electrodes sparking, then oilpump solenoid actuated, then if a flame is sensed by photocell, solenoid kept open.
if no flame, the photocell will cut feed to the pump solenoid and lock out.

mark properjob, February 2012