Tanzania asked ... How can i mend my sanyo fwbp505f q?    |    Mark Goodwin asked ... Mount field 725m ride on mower?    |    Joan Sorrentino asked ... Barcalounger issue?    |    David asked ... Not starting until I bang door closed?    |    Sharma asked ... Replacing pin for belt guard Ranch King Pro 14AT818H205?    |    Click here to ask your question

Hot water issue?

Halstead ace boiler c/h ok hot water intermitant. Changed diverter diaphram and dhw thermistor still issues. Could the heat exchanger be scaled up?
simpson, February 2012
had this b4 where worked ok on c/h but not on h/w ended up being the fan venturi partially blocked only highlighted itself on hot water because higher burner pressure in h/w mode

hig, February 2012
Hot water heat exchanger scale up need acid clean

ltg, February 2012