1 hour ago Don asked ... Find the charger or how to convert the battery?    |    Tanzania asked ... How can i mend my sanyo fwbp505f q?    |    Mark Goodwin asked ... Mount field 725m ride on mower?    |    Joan Sorrentino asked ... Barcalounger issue?    |    David asked ... Not starting until I bang door closed?    |    Click here to ask your question

britony combi se80 leaking?

my boiler is constantly leaking and losing pressure as a result, i have to top the pressure up every week
craig, October 2006
expansion vessel is flat at the back. call an engineer - or take off the case - open the pressure relief valve in the back right hand corner (red twist knob) in behind boiler you will find an orange disk anout the size of a car wheel with a foot pump connection on. pump this up to 1 bar, close pressure relief vale and re-rill. should sort it.

craig, plymouth, October 2006