Blaablaa asked ... How can I fix?    |    pete asked ... Flymo 330 turboglide?    |    keith asked ... Fuseboard( s) location of renault trafic t1100 1993?    |    Janet asked ... Neff B1641 door not closing at top?    |    Steve asked ... Gilera runner 180 vxr 2001 ignition replacement?    |    Click here to ask your question

Worcester Bosch 25si not igniting?

Due to the recent very wet weather and strong winds, my boiler has gone into fault with flashing red light, I have dried the boiler out, but when running both with hot water and heating the gas burners ignite, the go out after 10 to 20 seconds, this pattern repeats a few times then goes into flashing light over central heating control, the burner light on the boiler does not come on.

Graham
Graham, June 2012
Thanks AWOL the fault after downloading fault finding from Worcester Bosch, and testing turned out to be PCB faulty, probably caused by water leaking into boiler.

Thanks

Graham, June 2012
water on gas valve solenoid?

AWOL, June 2012